In laboratory and full-scal ignition tests, Envirotemp FR3 fluid has demonstrated greater fire resistance than other dielectric fluid types. Based on large-scale arc ignition testing, FM Global concluded that the probability of a pool fire evolving from Envirotemp FR3 fluid was so low that heat release rate need not be determined or considered for FM Global approval.
Based on large scale arc igintion and hot metal ignition tests, FM global recognizes Envirotemp FR3 fluid as an equivalent safegaurd to space separation, fire barriers, and fire supperssion systems for most installations.
FM Global Recognizes Envirotemp FR3 fluid as a component of Approved transformers per FM Global Standard 3990. Whne used in transformers containing 10,000 gallons of fluid or less, transformers separation distance to buildings and other equipment may be up to 1/10th the distance required for mineral oil filled transformers, without fire walls or deluge systems.
occupational Safety & Health Administration (OSHA) recognizes this FM Global standard as fitting the definition of a Listed and Labled Product per NEC Section 110-3(b). The standard permits Envirotemp FR3 fluid-filled transformer to be installed indoors, typically without sprinklers or vaults, with a minimum clearance to walls of just 3 feet (0.9M).
UL Standard 340 compares the fire hazard ratings of various fluids. Figure 3 shows the favorable rating assigned to Envirotemp FR3 fluid.